20 kV线路单相接地保护方案探讨

发表时间:2010-07-31  浏览量:1692  下载量:837
全部作者: 王通,刘皓明
作者单位: 河海大学能源与电气学院
摘 要: 通过对20 kV中性点经小电阻接地线路单相接地故障的仿真与分析,在现有零序两段式过电流保护的基础上,提出了运用零序功率方向保护解决单相高阻接地故障的方法,并且通过仿真比较了2种保护方法的性能。结果表明:零序功率方向保护在可靠性和灵敏性上都优于零序过流保护。
关 键 词: 电力系统及其自动化;20 kV线路;小电阻接地;单相高阻接地;零序功率方向保护
Title: Discussion on 20 kV branch single�phase to earth protection scheme
Author: WANG Tong, LIU Haoming
Organization: College of Energy and Electrics, Hohai University
Abstract: The neutral point usually grounds with low resistance in 20 kV distribution network. The traditional two zones zero�sequence over�current protection always fails to act in case of single phase high resistance earth fault. A new scheme is proposed in this paper, which can act correctly via directional zero�sequence power protection. Simulation and analysis are implemented. The results indicate that the proposed directional zero�sequence power protection is reliable and sensitive.
Key words: electric power system and automation; 20 kV branch; low�resistance grounding; high resistance earth fault; directional zero�sequence power protection
发表期数: 2010年7月第14期
引用格式: 王通,刘皓明. 20 kV线路单相接地保护方案探讨[J]. 中国科技论文在线精品论文,2010,3(14):1474-1478.
 